Page 46 Version 1.0 March 1, 2000
P571 = 0
P318 = 95
P052 = 21
P052 = 0
P571=0 Selects Autotransformer
P318 = 95%
Selects percentage of nominal
DC BUS voltage. In cases where
the input line voltage is
dependable a setting of 100% is
permissible.
With DC BUS connected to the
COMMON DC BUS of the system, set
P52=21 and provide a start command
at terminal X101, pin #9
The circuit identification test will take
about 10 seconds.
P052=0 Drive back to ready mode.
Standard Commissioning for a
Regenerative Rectifier with
Autotransformer is complete, after
adjusting only 10 parameters.