Vector SIMOVERT MASTERDRIVES 6SE70 VC Instructions d'exploitation Page 107

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 162
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 106
Vector Control Chassis Type Frequency Converter Parameterizing steps
SIEMENS AG 476 869 4070 76 J AB-74
SIMOVERT MASTERDRIVES Operating Instructions 9-43
Analog tachometer?
no yes
Adjust
tachometer
Adjust tachometer
Tachometer to ATI: See operating instructions for ATI
Tachometer to terminal strip: See function diagrams for analog
inputs
Analog tachometer present?
P115 = 5
Calculate motor model "Controller optimization"
Note:
Current flows through the motor, the rotor rotates!
After "P" is pressed, the alarm message "A080" appears.
The converter must be switched on within 20 seconds!
Wait until the converter is "Ready for ON" again (°009)
For fault "Fxxx", refer to chapter "Faults and alarms"
Wait
f, n, m control?
(P100 = 3, 4, 5)
no yes
P115 = 4
Calculate motor model "No-load measurement"
Note:
Current flows through the motor and the rotor rotates!
After "P" key is pressed, the alarm message "A080" appears.
The converter must be switched on within 20 seconds!
P536 = ?
Enter the dynamic performance of the speed control circuit
in %
Important for subsequent controller optimization.
Wait until the converter is powered-down
(Operating status "Ready for ON" (°009))
For fault "Fxxx", see chapter "Faults and alarms"
Wait
Finished
Vue de la page 106
1 2 ... 102 103 104 105 106 107 108 109 110 111 112 ... 161 162

Commentaires sur ces manuels

Pas de commentaire