Vector SIMOVERT MASTERDRIVES 6SE70 VC Instructions d'exploitation Page 146

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 162
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 145
Maintenance Vector Control Chassis Type Frequency Converter
476 869 4070 76 J AB-74 Siemens AG
12-6 Operating Instructions SIMOVERT MASTERDRIVES
12.7 Replacing the SML and the SMU
SML: Snubber Module Lower
SMU: Snubber Module Upper
Remove the capacitor battery.
Undo the fixing screws (4 x M8, 8 - 10 Nm or 4 x M6, 2.5 - 5 Nm, 1 x
M4, max 1.8 Nm).
Remove the modules.
Install the new modules in the reverse sequence.
12.8 Removing and installing the module busbars
(from type G)
Remove the capacitor battery.
Undo the screws of the module busbars.
M8 power connections
M6 fastening on spacers
M4 circuit.
Take out the insulation of the SMU / SML.
Lift out the module busbars.
The spacing between the plus busbar and the minus busbar must be at
least 4 mm. In order to install the module busbars, you must therefore
use a template, e.g. a 4 mm thick piece of plastic.
Place the module busbars and SMU/SML insulation on spacer bolts
and fix in place (M6).
Place the template instead of the DC link bus module in the module
busbars.
Locate the SMU and SML and tighten the modular connections (M8,
8 - 10 Nm, M6, 2.5 - 5 Nm).
Screw the nuts tight on the spacer bolts (6 Nm).
Connect the circuit resistors (M4, 1.8 Nm).
Tighten the power connections (M8, 13 Nm).
Remove the template from the module busbars.
Module screw
connection
+
Module
screw con-
nection
Template 4 mm
4
Fig. 12-4 Installing the module busbars
Removal
Installation
NOTE
Vue de la page 145
1 2 ... 141 142 143 144 145 146 147 148 149 150 151 ... 161 162

Commentaires sur ces manuels