Technical Data Vector Control Chassis Type Frequency Converter
476 869 4070 76 J AB-74 Siemens AG
4-18 Operating Instructions SIMOVERT MASTERDRIVES
* The sound level was determined under the following boundary
conditions:
Distance to the unit 1m, height above floor level 1 m, distance to the
next reflecting wall 4 m, room height 6 m.
The chassis were installed in Siemens 8MC cabinets without any
special soundproofing measures.
Fan voltage/frequency V/Hz 230/50 230/60
Current requirement A 2.45 3.6
Sound pressure level IP20 dB(A) Table values Table values + 1.0
Sound pressure level IP42 dB(A) Table values Table values + 0.5
Sound pressure level IP54 dB(A) Table values Table values
Table 4-11 Operating data of fan
4.4 Venting the heat sinks
The position of the connecting elements is shown in the annex
"Dimension drawings" of the VC Compendium.
Venting must be performed when the equipment is disconnected
from the supply.
Dismantle the lock screw in front of the actual vent valve.
Perform venting.
Close the vent cock.
Tighten the lock screw again.
Check for tightness.